Last Modified: 07-31-2024 6.11:8.1.0 Doc ID: RM1000000026PWR
Model Year Start: 2023 Model: Corolla HV Prod Date Range: [09/2022 -           ]
Title: HYBRID / BATTERY CONTROL: MOTOR GENERATOR CONTROL SYSTEM (for LITHIUM-ION BATTERY with PA10): P06B01C,...,P32CF87; Generator Control Module Position Sensor REF Power Source Circuit Voltage Out of Range; 2023 - 2025 MY Corolla HV [09/2022 -        ]

DTC

P06B01C

Generator Control Module Position Sensor REF Power Source Circuit Voltage Out of Range

DTC

P06B31C

Drive Motor "B" Control Module Position Sensor REF Power Source Circuit Voltage Out of Range

DTC

P06B31F

Drive Motor "B" Control Module Position Sensor REF Power Source Circuit Intermittent

DTC

P0A1A49

Generator Control Module Internal Electronic Failure

DTC

P0A1B47

Drive Motor "A" Control Module Watchdog / Safety MC Failure

DTC

P0A1B49

Drive Motor "A" Control Module Internal Electronic Failure

DTC

P0A1C49

Drive Motor "B" Control Module Internal Electronic Failure

DTC

P1C2A1C

Generator A/D Converter Circuit Circuit Voltage Out of Range

DTC

P1C2A71

Generator A/D Converter Circuit Actuator Stuck

DTC

P1C2B1C

Drive Motor "A" Control Module A/D Converter Circuit Voltage Out of Range

DTC

P1C2B49

Drive Motor "A" Control Module A/D Converter Circuit Internal Electronic Failure

DTC

P1C2B71

Drive Motor "A" Control Module A/D Converter Circuit Actuator Stuck

DTC

P1C2C1C

Drive Motor "B" Control Module AD Converter Circuit Voltage Out of Range

DTC

P1C2C71

Drive Motor "B" Control Module A/D Converter Circuit Actuator Stuck

DTC

P1C601F

Generator Control Module Position Sensor REF Power Source Circuit Intermittent

DTC

P1C621F

Generator Control Module Offset Power Circuit Intermittent

DTC

P26DF1C

Generator Control Module Position Sensor REF Power Source Circuit Voltage Out of Range

DTC

P26DF1F

Generator Control Module Position Sensor REF Power Source Circuit Intermittent

DTC

P310A1F

Communication Error from Drive Motor "B" to Drive Motor "A" Circuit Intermittent

DTC

P310A83

Communication Error from Drive Motor "B" to Drive Motor "A" Value of Signal Protection Calculation Incorrect

DTC

P310A86

Communication Error from Drive Motor "B" to Drive Motor "A" Signal (Some Circuit Quantity, Reported via Serial Data) Invalid

DTC

P310A87

Communication Error from Drive Motor "B" to Drive Motor "A" Missing Message

DTC

P310B1F

Communication Error from Drive Motor "A" to Drive Motor "B" Circuit Intermittent

DTC

P310B83

Communication Error from Drive Motor "A" to Drive Motor "B" Value of Signal Protection Calculation Incorrect

DTC

P310B86

Communication Error from Drive Motor "A" to Drive Motor "B" Signal (Some Circuit Quantity, Reported via Serial Data) Invalid

DTC

P310B87

Communication Error from Drive Motor "A" to Drive Motor "B" Missing Message

DTC

P313383

Communication Error from Generator to Drive Motor "A" Value of Signal Protection Calculation Incorrect

DTC

P313386

Communication Error from Generator to Drive Motor "A" Signal Invalid

DTC

P313387

Communication Error from Generator to Drive Motor "A" Missing Message

DTC

P313483

Communication Error from Drive Motor "A" to Generator Value of Signal Protection Calculation Incorrect

DTC

P313486

Communication Error from Drive Motor "A" to Generator Signal Invalid

DTC

P313487

Communication Error from Drive Motor "A" to Generator Missing Message

DTC

P32BF1F

Lost Communication between Drive Motor "A" and "B" (Drive Motor "A") Circuit Intermittent

DTC

P32BF83

Lost Communication between Drive Motor "A" and "B" (Drive Motor "A") Value of Signal Protection Calculation Incorrect

DTC

P32BF86

Lost Communication between Drive Motor "A" and "B" (Drive Motor "A") Signal (Some Circuit Quantity, Reported via Serial Data) Invalid

DTC

P32BF87

Lost Communication between Drive Motor "A" and "B" (Drive Motor "A") Missing Message

DTC

P32CF1F

Lost Communication between Drive Motor "A" and "B" (Drive Motor "B") Circuit Intermittent

DTC

P32CF83

Lost Communication between Drive Motor "A" and "B" (Drive Motor "B") Value of Signal Protection Calculation Incorrect

DTC

P32CF86

Lost Communication between Drive Motor "A" and "B" (Drive Motor "B") Signal (Some Circuit Quantity, Reported via Serial Data) Invalid

DTC

P32CF87

Lost Communication between Drive Motor "A" and "B" (Drive Motor "B") Missing Message

DESCRIPTION

The motor generator control ECU (MG ECU), which is built into the inverter with converter assembly, monitors its internal operation and will store DTCs if it detects a malfunction. If any of the following DTCs are output, replace the inverter with converter assembly.

DTC No.

Detection Item

DTC Detection Condition

Trouble Area

MIL

Warning Indicate

Note

P06B01C

Generator Control Module Position Sensor REF Power Source Circuit Voltage Out of Range

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P06B0

P06B31C

Drive Motor "B" Control Module Position Sensor REF Power Source Circuit Voltage Out of Range

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P06B3

P06B31F

Drive Motor "B" Control Module Position Sensor REF Power Source Circuit Intermittent

Motor generator control ECU internal malfunction detected when DTC P0C7917, P0E5717, P0D3319, P1C5D19, P1C5F19 or P1C5E19 is stored.

(1 trip detection logic)

Inverter with converter assembly

Does not come on

Master Warning:

Does not come on

SAE Code:

P1C61

P0A1A49

Generator Control Module Internal Electronic Failure

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P0A1A

P0A1B47

Drive Motor "A" Control Module Watchdog / Safety MC Failure

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P0A1B

P0A1B49

Drive Motor "A" Control Module Internal Electronic Failure

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P0A1B

P0A1C49

Drive Motor "B" Control Module Internal Electronic Failure

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P0A1C

P1C2A1C

Generator A/D Converter Circuit Circuit Voltage Out of Range

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P1C2A

P1C2A71

Generator A/D Converter Circuit Actuator Stuck

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P1C2A

P1C2B1C

Drive Motor "A" Control Module A/D Converter Circuit Voltage Out of Range

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P1C2B

P1C2B49

Drive Motor "A" Control Module A/D Converter Circuit Internal Electronic Failure

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P1C2B

P1C2B71

Drive Motor "A" Control Module A/D Converter Circuit Actuator Stuck

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P1C2B

P1C2C1C

Drive Motor "B" Control Module AD Converter Circuit Voltage Out of Range

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P1C2C

P1C2C71

Drive Motor "B" Control Module A/D Converter Circuit Actuator Stuck

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P1C2C

P1C601F

Generator Control Module Position Sensor REF Power Source Circuit Intermittent

Motor generator control ECU internal malfunction detected when DTC P0C7917, P0E5717, P0D3319, P1C5D19, P1C5F19 or P1C5E19 is stored.

(1 trip detection logic)

Inverter with converter assembly

Does not come on

Master Warning:

Does not come on

SAE Code:

P1C60

P1C621F

Generator Control Module Offset Power Circuit Intermittent

Motor generator control ECU internal malfunction detected when DTC P0C7917, P0E5717, P0D3319, P1C5D19, P1C5F19 or P1C5E19 is stored.

(1 trip detection logic)

Inverter with converter assembly

Does not come on

Master Warning:

Does not come on

SAE Code:

P1C62

P26DF1C

Generator Control Module Position Sensor REF Power Source Circuit Voltage Out of Range

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P26DF

P26DF1F

Generator Control Module Position Sensor REF Power Source Circuit Intermittent

Motor generator control ECU internal malfunction detected when DTC P0C7917, P0E5717, P0D3319, P1C5D19, P1C5F19 or P1C5E19 is stored.

(1 trip detection logic)

Inverter with converter assembly

Does not come on

Master Warning:

Does not come on

SAE Code:

P19F7

P310A1F

Communication Error from Drive Motor "B" to Drive Motor "A" Circuit Intermittent

Motor generator control ECU internal malfunction detected when DTC P0C7917, P0E5717, P0D3319, P1C5D19, P1C5F19 or P1C5E19 is stored.

(1 trip detection logic)

Inverter with converter assembly

Does not come on

Master Warning:

Does not come on

SAE Code:

P310A

P310A83

Communication Error from Drive Motor "B" to Drive Motor "A" Value of Signal Protection Calculation Incorrect

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P310A

P310A86

Communication Error from Drive Motor "B" to Drive Motor "A" Signal (Some Circuit Quantity, Reported via Serial Data) Invalid

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P310A

P310A87

Communication Error from Drive Motor "B" to Drive Motor "A" Missing Message

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P310A

P310B1F

Communication Error from Drive Motor "A" to Drive Motor "B" Circuit Intermittent

Motor generator control ECU internal malfunction detected when DTC P0C7917, P0E5717, P0D3319, P1C5D19, P1C5F19 or P1C5E19 is stored.

(1 trip detection logic)

Inverter with converter assembly

Does not come on

Master Warning:

Does not come on

SAE Code:

P310B

P310B83

Communication Error from Drive Motor "A" to Drive Motor "B" Value of Signal Protection Calculation Incorrect

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P310B

P310B86

Communication Error from Drive Motor "A" to Drive Motor "B" Signal (Some Circuit Quantity, Reported via Serial Data) Invalid

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P310B

P310B87

Communication Error from Drive Motor "A" to Drive Motor "B" Missing Message

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P310B

P313383

Communication Error from Generator to Drive Motor "A" Value of Signal Protection Calculation Incorrect

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P3133

P313386

Communication Error from Generator to Drive Motor "A" Signal Invalid

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P3133

P313387

Communication Error from Generator to Drive Motor "A" Missing Message

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P3133

P313483

Communication Error from Drive Motor "A" to Generator Value of Signal Protection Calculation Incorrect

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P3134

P313486

Communication Error from Drive Motor "A" to Generator Signal Invalid

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P3134

P313487

Communication Error from Drive Motor "A" to Generator Missing Message

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P3134

P32BF1F

Lost Communication between Drive Motor "A" and "B" (Drive Motor "A") Circuit Intermittent

Motor generator control ECU internal malfunction detected when DTC P0C7917, P0E5717, P0D3319, P1C5D19, P1C5F19 or P1C5E19 is stored.

(1 trip detection logic)

Inverter with converter assembly

Does not come on

Master Warning:

Does not come on

SAE Code:

P32BF

P32BF83

Lost Communication between Drive Motor "A" and "B" (Drive Motor "A") Value of Signal Protection Calculation Incorrect

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P32BF

P32BF86

Lost Communication between Drive Motor "A" and "B" (Drive Motor "A") Signal (Some Circuit Quantity, Reported via Serial Data) Invalid

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P32BF

P32BF87

Lost Communication between Drive Motor "A" and "B" (Drive Motor "A") Missing Message

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P32BF

P32CF1F

Lost Communication between Drive Motor "A" and "B" (Drive Motor "B") Circuit Intermittent

Motor generator control ECU internal malfunction detected when DTC P0C7917, P0E5717, P0D3319, P1C5D19, P1C5F19 or P1C5E19 is stored.

(1 trip detection logic)

Inverter with converter assembly

Does not come on

Master Warning:

Does not come on

SAE Code:

P32CF

P32CF83

Lost Communication between Drive Motor "A" and "B" (Drive Motor "B") Value of Signal Protection Calculation Incorrect

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P32CF

P32CF86

Lost Communication between Drive Motor "A" and "B" (Drive Motor "B") Signal (Some Circuit Quantity, Reported via Serial Data) Invalid

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P32CF

P32CF87

Lost Communication between Drive Motor "A" and "B" (Drive Motor "B") Missing Message

Motor generator control ECU internal malfunction

(1 trip detection logic)

Inverter with converter assembly

Comes on

Master Warning:

Comes on

SAE Code:

P32CF

MONITOR DESCRIPTION

The motor generator control ECU monitors its internal operation and will illuminate the MIL and store a DTC if it detects a malfunction.

MONITOR STRATEGY

Related DTCs

P06B0 (INF P06B01C): Sensor Power Supply "A" Circuit (31V for Drive Motor "A"/Generator)

P06B3 (INF P06B31C): Sensor Power Supply "B" Circuit (31V for Drive Motor "B"/Generator)

P06D6 (INF P06D61C): Sensor Reference Voltage "F" Circuit (2.5V for Drive Motor "A"/Generator)

P0A1A (INF P0A1A49): Generator Control Module

P0A1B (INF P0A1B47/P0A1B49): Drive Motor "A" Control Module

P0A1C (INF P0A1C49): Drive Motor "B" Control Module

P19F8 (INF P19F81C): Sensor Reference Voltage "G" Circuit (2.5V for Generator)

P19F9 (INF P19F91C): Sensor Reference Voltage "H" Circuit (2.5V for Drive Motor "B"/Generator)

P1C2A (INF P1C2A1C/P1C2A71): Generator Control Module A/D Processing

P1C2B (INF P1C2B49/P1C2B1C/P1C2B71): Drive Motor "A" Control Module A/D Processing

P1C2C (INF P1C2C1C/P1C2C71): Drive Motor "B" Control Module A/D Processing

P26DF (INF P26DF1C): Sensor Power Supply "D" Circuit (31V for Generator)

P310A (INF P310A83/P310A86/P310A87): Lost Communication With Drive Motor "B" Control Module

P310B (INF P310B83/P310B86/P310B87): Lost Communication With Drive Motor "A" Control Module (Drive Motor "B" Control Module)

P3133 (INF P313383/P313386/P313387): Lost Communication With Generator Control Module

P3134 (INF P313483/P313486/P313487): Lost Communication With Drive Motor "A" Control Module

P32BF (INF P32BF83/P32BF86/P32BF87): Lost Communication With Drive Motor "B" Control Module (Generator Control Module)

P32CF (INF P32CF83/P32CF86/P32CF87): Lost Communication With Generator Control Module (Drive Motor "B" Control Module)

Required sensors/components

Motor generator control ECU

Frequency of operation

Continuous

Duration

TMC's intellectual property

MIL operation

Immediately

Sequence of operation

None

TYPICAL ENABLING CONDITIONS

The monitor will run whenever the following DTCs are not stored

TMC's intellectual property

Other conditions belong to TMC's intellectual property

-

TYPICAL MALFUNCTION THRESHOLDS

TMC's intellectual property

-

COMPONENT OPERATING RANGE

Motor generator control ECU

DTC P06B0 (INF P06B01C) is not detected

DTC P06B3 (INF P06B31C) is not detected

DTC P06D6 (INF P06D61C) is not detected

DTC P0A1A (INF P0A1A49) is not detected

DTC P0A1B (INF P0A1B47/P0A1B49) is not detected

DTC P0A1C (INF P0A1C49) is not detected

DTC P19F8 (INF P19F81C) is not detected

DTC P19F9 (INF P19F91C) is not detected

DTC P1C2A (INF P1C2A1C/P1C2A71) is not detected

DTC P1C2B (INF P1C2B49/P1C2B1C/P1C2B71) is not detected

DTC P1C2C (INF P1C2C1C/P1C2C71) is not detected

DTC P26DF (INF P26DF1C) is not detected

DTC P310A (INF P310A83/P310A86/P310A87) is not detected

DTC P310B (INF P310B83/P310B86/P310B87) is not detected

DTC P3133 (INF P313383/P313386/P313387) is not detected

DTC P3134 (INF P313483/P313486/P313487) is not detected

DTC P32BF (INF P32BF83/P32BF86/P32BF87) is not detected

DTC P32CF (INF P32CF83/P32CF86/P32CF87) is not detected

CONFIRMATION DRIVING PATTERN

HINT:

  • After repair has been completed, clear the DTC and then check that the vehicle has returned to normal by performing the following All Readiness check procedure.

    Click here 2023 - 2025 MY Corolla HV [09/2022 -        ]; HYBRID / BATTERY CONTROL: MOTOR GENERATOR CONTROL SYSTEM (for LITHIUM-ION BATTERY with PA10): UTILITY

  • When clearing the permanent DTCs, refer to the "CLEAR PERMANENT DTC" procedure.

    Click here 2023 - 2025 MY Corolla HV [09/2022 -        ]; HYBRID / BATTERY CONTROL: MOTOR GENERATOR CONTROL SYSTEM (for LITHIUM-ION BATTERY with PA10): DTC CHECK / CLEAR

  1. Clear the DTCs (even if no DTCs are stored, perform the clear DTC procedure).
  2. Turn the ignition switch off and wait for 2 minutes or more.
  3. Turn the ignition switch to ON and wait for 15 seconds or more. [*1]

    HINT:

    [*1]: Normal judgment procedure.

    The normal judgment procedure is used to complete DTC judgment and also used when clearing permanent DTCs.

  4. Enter the following menus: Powertrain / Motor Generator / Utility / All Readiness.
  5. Check the DTC judgment result.

    HINT:

    • If the judgment result shows NORMAL, the system is normal.
    • If the judgment result shows ABNORMAL, the system has a malfunction.
    • If the judgment result shows INCOMPLETE, perform the normal judgment procedure again.

PROCEDURE

1.

REPLACE INVERTER WITH CONVERTER ASSEMBLY

Click here 2023 - 2025 MY Corolla Corolla HV [09/2022 -        ]; HYBRID / BATTERY CONTROL: INVERTER WITH CONVERTER: REMOVAL

NEXT

COMPLETED