Room Temperature Sensor
|
Cooler (room temp. sensor) thermistor
|
Min.: -6.50°C (20.30°F)
Max.: 57.25°C (135.05°F)
|
Actual cabin temperature displayed
|
Cooler (room temp. sensor) thermistor circuit malfunction
-
When open circuit: -6.50°C (20.30°F)
-
When short circuit: 57.25°C (135.05°F)
|
Ambient Temp Sensor
|
Thermistor assembly
|
Min.: -23.30°C (-9.94°F)
Max.: 65.95°C (150.71°F)
|
Actual ambient temperature displayed
|
Thermistor assembly circuit malfunction
-
When open circuit: -23.30°C (-9.94°F)
-
When short circuit: 65.95°C (150.71°F)
|
Adjusted Ambient Temp
|
Adjusted ambient temperature
|
Min.: -30.80°C (-23.44°F)
Max.: 50.80°C (123.44°F)
|
Adjust ambient temperature displayed
|
Air conditioning amplifier assembly circuit malfunction
|
Evaporator Fin Thermistor
|
No. 1 cooler thermistor
|
Min.: -29.70°C (-21.46°F)
Max.: 59.55°C (139.19°F)
|
Actual evaporator temperature displayed
|
No. 1 cooler thermistor circuit malfunction
-
When open circuit: -29.70°C (-21.46°F)
-
When short circuit: 59.55°C (139.19°F)
|
Evaporator Target Temp
|
Evaporator target temperature
|
Min.: -327.68°C (-557.82°F)
Max.: 327.67°C (621.81°F)
|
Evaporator target temperature displayed
|
No. 1 cooler thermistor circuit malfunction
-
When open circuit: -327.68°C (-557.82°F)
-
When short circuit: 327.67°C (621.81°F)
|
Solar Sensor (D Side)
|
Automatic light control sensor
|
Min.: 0
Max.: 255
|
Automatic light control sensor value increases as brightness increases
|
Automatic light control sensor circuit malfunction
-
When open circuit: 0
-
When short circuit: 255
|
Engine Coolant Temp
|
Engine coolant temperature sensor
|
Min.: 1.30°C (34.34°F)
Max.: 90.55°C (194.99°F)
|
Actual engine coolant temperature displayed
|
-
SFI system malfunction
-
CAN communication system malfunction
|
Blower Motor Speed Level
|
Blower motor speed level
|
Min.: 0
Max.: 31
|
Displayed speed level increases in range between 0 and 31 as blower motor speed increases
|
Blower motor with fan sub-assembly circuit malfunction
|
Regulator Pressure Sensor
|
Air conditioner pressure sensor
|
Min.: -456.68 kPaG
Max.: 3294.37 kPaG
|
Actual refrigerant pressure displayed
|
-
Refrigerant line (gas leak etc.)
-
Air conditioner pressure sensor circuit malfunction
|
Air Outlet Servo Pulse (R)
|
No. 2 air conditioning radiator damper servo sub-assembly target pulse
|
Min.: 128
Max.: 383
|
-
FACE: 250 (pulse)
-
B/L: 281 (pulse)
-
FOOT: 287 (pulse)
-
F/D: 297 (pulse)
-
SHUT: 250 (pulse)
-
D/F: 272 (pulse)
|
No. 2 air conditioning radiator damper servo sub-assembly circuit malfunction*1
|
Air Outlet Servo Actual Pls(R)
|
No. 2 air conditioning radiator damper servo sub-assembly actual pulse
|
Min.: 128
Max.: 383
|
-
FACE: 250 (pulse)
-
B/L: 281 (pulse)
-
FOOT: 287 (pulse)
-
F/D: 297 (pulse)
-
SHUT: 250 (pulse)
-
D/F: 272 (pulse)
|
No. 2 air conditioning radiator damper servo sub-assembly circuit malfunction*1
|
Air Mix Servo Targ Pulse(D)
|
No. 1 air conditioning radiator damper servo sub-assembly target pulse
|
Min.: 128
Max.: 383
|
-
MAX COLD: 257 (pulse)
-
MAX HOT: 165 (pulse)
|
No. 1 air conditioning radiator damper servo sub-assembly circuit malfunction
|
Air Mix Servo Actual Pulse(D)
|
No. 1 air conditioning radiator damper servo sub-assembly actual pulse
|
Min.: 128
Max.: 383
|
-
MAX COLD: 257 (pulse)
-
MAX HOT: 165 (pulse)
|
No. 1 air conditioning radiator damper servo sub-assembly circuit malfunction
|
Air Outlet Servo Pulse (D)
|
No. 3 air conditioning radiator damper servo sub-assembly target pulse
|
Min.: 128
Max.: 383
|
-
FACE-R: 271 (pulse)
-
FACE: 256 (pulse)
-
FACE1: 256 (pulse)
-
FACE2: 256 (pulse)
-
B/L: 245 (pulse)
-
B/L2: 245 (pulse)
-
FOOT-R: 215 (pulse)
-
FOOT: 215 (pulse)
-
FOOT-D: 207 (pulse)
-
FOOT-0: 224 (pulse)
-
F/D: 192 (pulse)
-
DEF-FOOT: 173 (pulse)
-
DEF or SHUT: 164 (pulse)
-
S-FLOW: 278 (pulse)
|
No. 3 air conditioning radiator damper servo sub-assembly circuit malfunction
|
Air Outlet Servo Actu Pulse(D)
|
No. 3 air conditioning radiator damper servo sub-assembly target pulse
|
Min.: 128
Max.: 383
|
-
FACE-R: 271 (pulse)
-
FACE: 256 (pulse)
-
FACE1: 256 (pulse)
-
FACE2: 256 (pulse)
-
B/L: 245 (pulse)
-
B/L2: 245 (pulse)
-
FOOT-R: 215 (pulse)
-
FOOT: 215 (pulse)
-
FOOT-D: 207 (pulse)
-
FOOT-0: 224 (pulse)
-
F/D: 192 (pulse)
-
DEF-FOOT: 173 (pulse)
-
DEF or SHUT: 164 (pulse)
-
S-FLOW: 278 (pulse)
|
No. 3 air conditioning radiator damper servo sub-assembly circuit malfunction
|
Air Outlet Servo Targ Pulse(P)
|
No. 1 air conditioning radiator damper servo sub-assembly target pulse
|
Min.: 128
Max.: 383
|
-
FACE-R: 241 (pulse)
-
FACE: 256 (pulse)
-
FACE1: 256 (pulse)
-
FACE2: 256 (pulse)
-
B/L: 267 (pulse)
-
B/L2: 267 (pulse)
-
FOOT-R: 297 (pulse)
-
FOOT: 297 (pulse)
-
FOOT-D: 305 (pulse)
-
FOOT-0: 288 (pulse)
-
F/D: 320 (pulse)
-
DEF-FOOT: 339 (pulse)
-
DEF or SHUT: 348 (pulse)
-
S-FLOW: 234 (pulse)
|
No. 1 air conditioning radiator damper servo sub-assembly circuit malfunction
|
Air Outlet Servo Actu Pulse(P)
|
No. 1 air conditioning radiator damper servo sub-assembly target pulse
|
Min.: 128
Max.: 383
|
-
FACE-R: 241 (pulse)
-
FACE: 256 (pulse)
-
FACE1: 256 (pulse)
-
FACE2: 256 (pulse)
-
B/L: 267 (pulse)
-
B/L2: 267 (pulse)
-
FOOT-R: 297 (pulse)
-
FOOT: 297 (pulse)
-
FOOT-D: 305 (pulse)
-
FOOT-0: 288 (pulse)
-
F/D: 320 (pulse)
-
DEF-FOOT: 339 (pulse)
-
DEF or SHUT: 348 (pulse)
-
S-FLOW: 234 (pulse)
|
No. 1 air conditioning radiator damper servo sub-assembly circuit malfunction
|
Air Inlet Damper Targ Pulse
|
No. 1 blower damper servo sub-assembly target pulse
|
Min.: 128
Max.: 383
|
-
Recirculation: 256 (pulse)
-
Fresh: 220 (pulse)
|
No. 1 blower damper servo sub-assembly circuit malfunction
|
Air Inlet Damper Actual Pulse
|
No. 1 blower damper servo sub-assembly actual pulse
|
Min.: 128
Max.: 383
|
-
Recirculation: 256 (pulse)
-
Fresh: 220 (pulse)
|
No. 1 blower damper servo sub-assembly circuit malfunction
|
Electric Heater Count
|
Maximum electric heater operation level
|
Min.: 0
Max.: 3
|
Maximum possible operation level of electric heater displayed
|
PTC heater circuit malfunction*2
|
Electric Heater Active Level
|
Actual electric heater operation level
|
Min.: 0
Max.: 3
|
Actual operation level of electric heater displayed
|
PTC heater circuit malfunction*2
|
Compressor Speed
|
Compressor speed
|
Min.: 0 rpm
Max.: 65535 rpm
|
Actual compressor speed displayed
|
-
|
Compressor Target Speed
|
Compressor target speed
|
Min.: 0 rpm
Max.: 65535 rpm
|
Compressor target speed displayed
|
-
|
Shift Set Temperature
|
Shift set temperature
|
2C decr, 1C decr, Normal, 1C incr or 2C incr
|
Customized value displayed
|
-
|
Air Inlet Mode
|
Air inlet mode
|
Auto or Manual
|
Customized value displayed
|
-
|
Compressor Mode
|
Compressor mode
|
Auto or Manual
|
Customized value displayed
|
-
|
Noise and Vibration Reduction
|
Function to change the speed of the compressor when set to ON
|
OFF or ON
|
Customized value displayed
|
-
|
ECO MODE Cancel
|
Function to cancel ECO mode when set to ON
|
OFF or ON
|
Customized value displayed
|
-
|
Refrigerant Shortage Check
|
Refrigerant shortage check
|
ON or OFF
|
Customized value displayed
|
-
|
Fan speed increment control
|
Fan speed increment control
|
Slow, Normal or Fast
|
Customized value displayed
|
-
|
Foot/DEF Auto Mode
|
Foot/defroster auto mode
|
ON or OFF
|
Customized value displayed
|
-
|
Foot/DEF Auto Blow Up
|
Foot/defroster auto blower speed increase
|
ON or OFF
|
Customized value displayed
|
-
|
Ambient Temperature Shift
|
Ambient temperature shift
|
3C decr, 2C decr, 1C decr, Normal, 1C incr, 2C incr or 3C incr
|
Customized value displayed
|
-
|
Compressor Drive Check
|
Compressor drive check
|
OK or NG
|
OK: Compressor drives
NG: Compressor does not drive
|
-
|
Refrigerant Gas Type
|
Refrigerant gas type
|
R134a or 1234yf
|
Refrigerant gas type displayed
|
-
|
Set Temperature (D Side)
|
Driver side set temperature
|
Min.: MAX COLD
Max.: MAX HOT
|
Driver side set temperature displayed
|
-
|
Outside Air Mode Auto Switch Function
|
Outside air mode auto switch function
|
ON or OFF
|
Customized value displayed
|
-
|
S-FLOW Control Auto Function
|
S-FLOW control auto function
|
ON or OFF
|
Customized value displayed
|
-
|
Number of Trouble Codes
|
Number of trouble codes
|
Min.: 0
Max.: 255
|
Number of DTCs displayed
|
-
|
Refrigerant High Pressure History
|
Refrigerant high pressure history
|
Min.: 0
Max.: 255
|
Number of times refrigerant high pressure history stored displayed
|
*3
|