                        | Title: HEATING / AIR CONDITIONING: REFRIGERANT: ON-VEHICLE INSPECTION; 2019 - 2022 MY Avalon Avalon HV [04/2018 -        ] |  ON-VEHICLE INSPECTIONPROCEDURE1. INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET HINT: The following examples show the readings of a manifold gauge set and the corresponding air conditioning system problems. (a) Read the manifold gauge pressure when the following conditions are met: 
                     
                        
The doors are fully open.
The engine is idling (for Gasoline Model) or power switch is on (READY) (for HV Model).
The A/C switch is on.
The temperature is set to max cold.
The blower speed is set to high.
The temperature at the air inlet with recirculate selected is 30 to 35°C (86 to 95°F).
 
                     
                        
                           | (1) Normal functioning air conditioning system Gauge Reading
                                 
                                 
                                 
                                    
                                       | Pressure Side | Refrigerant Volume |  
                                       | Low | 150 to 250 kPa (1.5 to 2.5 kgf/cm2, 22 to 36 psi) |  
                                       | High | 1370 to 1570 kPa (14.0 to 16.0 kgf/cm2, 199 to 228 psi) |  |  |  (2) Abnormally functioning air conditioning system   
                     
                        
During operation, pressure on low pressure side cycles between normal and vacuum
                              
                                 
                                 
                              
                              
                                 
                                    | Symptom | Air conditioning system periodically cools and then fails to cool |  
                                    | Probable Cause | Moisture in air conditioning system freezes at expansion valve orifice, causing refrigerant to temporarily stop circulating |  
                                    | After system stops and warms up again, ice melts and normal operation is temporarily restored |  
                                    | Diagnosis | Cooler dryer (integrated into condenser tank) saturated with moisture |  
                                    | Moisture in air conditioning system is freezing at expansion valve orifice and blocking circulation of refrigerant |  
                                    | Corrective Actions | Replace cooler dryer |  
                                    | Remove moisture by repeatedly evacuating air from air conditioning system |  
                                    | Recharge air conditioning system with proper amount of new or purified refrigerant |  HINT: For the example above, moisture is present in the air conditioning system.
Pressure is low on both low and high pressure side
  
                              
                                 
                                 
                              
                              
                                 
                                    | Symptom | Air conditioning system does not cool effectively |  
                                    | Insufficient cooling performance |  
                                    | Probable Cause | Refrigerant leaks from air conditioning system |  
                                    | Diagnosis | Insufficient refrigerant |  
                                    | Refrigerant leaking |  
                                    | Corrective Actions | Check for refrigerant leaks and repair if necessary |  
                                    | Recharge air conditioning system with proper amount of new or purified refrigerant |  
                                    | If gauges indicate pressure of close to 0, then it is necessary to evacuate air conditioning system after repairing leaks |  HINT: For the example above, there is insufficient refrigerant.
Pressure is low on both low and high pressure side
  
                              
                                 
                                 
                              
                              
                                 
                                    | Symptom | Air conditioning system does not cool effectively |  
                                    | Frost exists on pipe from condenser to evaporator unit |  
                                    | Probable Cause | Refrigerant flow is obstructed by dirt inside pipes of condenser core |  
                                    | Diagnosis | Condenser is clogged |  
                                    | Corrective Actions | Replace condenser |  HINT: For the example above, there is poor circulation of refrigerant.
Vacuum is indicated on low pressure side and very low pressure is indicated on high pressure side
  
                              
                                 
                                 
                              
                              
                                 
                                    | Symptom | Air conditioning system does not cool effectively (System may cool occasionally) |  
                                    | Frost or condensation is seen on piping on both sides of receiver/dryer or expansion valve |  
                                    | Probable Cause | Refrigerant flow is obstructed by moisture or dirt in air conditioning system |  
                                    | Expansion valve is stuck closed |  
                                    | Diagnosis | Refrigerant does not circulate |  
                                    | Corrective Actions | Replace expansion valve |  
                                    | Replace condenser |  
                                    | Evacuate air conditioning system and recharge with proper amount of new or purified refrigerant |  HINT: For the example above, the refrigerant does not circulate.
Pressure is too high on both low and high pressure side
  
                              
                                 
                                 
                              
                              
                                 
                                    | Symptom | Air conditioning system does not cool effectively |  
                                    | Probable Cause | Unable to provide sufficient performance due to excessive amount of refrigerant |  
                                    | Cooling effectiveness of condenser is insufficient |  
                                    | Diagnosis | Excessive amount of refrigerant in air conditioning system because excessive refrigerant was added during recharging |  
                                    | Cooling effectiveness of condenser is insufficient because condenser fins are clogged or cooling fan is faulty |  
                                    | Corrective Actions | Clean condenser |  
                                    | Check operation of condenser cooling fan |  
                                    | If condenser is clean and fan operation is normal, check amount of refrigerant and recharge air conditioning system with proper amount of new or purified refrigerant |  HINT: For the example above, the air conditioning system is overcharged or cooling effectiveness of condenser is insufficient.
Pressure is too high on both low and high pressure side
  
                              
                                 
                                 
                              
                              
                                 
                                    | Symptom | Air conditioning system does not cool |  
                                    | The low pressure piping is too hot to touch |  
                                    | Probable Cause | Air in air conditioning system |  
                                    | Diagnosis | Air present in air conditioning system |  
                                    | Insufficient vacuum purging when evacuating air conditioning system |  
                                    | Corrective Actions | Replace cooler dryer |  
                                    | Check compressor oil to see if it is dirty or insufficient |  
                                    | Evacuate air conditioning system and recharge it with new or purified refrigerant |  NOTICE: These gauge indications occur when the air conditioning system has been left open and then recharged without evacuating the system. HINT: For the example above, air is present in the air conditioning system.
Pressure is too high on both low and high pressure side
  
                              
                                 
                                 
                              
                              
                                 
                                    | Symptom | Air conditioning system does not cool effectively |  
                                    | Frost or large amount of condensation on piping on low pressure side |  
                                    | Probable Cause | Expansion valve may be stuck open or metering refrigerant incorrectly |  
                                    | Diagnosis | Excessive refrigerant in low pressure piping |  
                                    | Expansion valve open too wide |  
                                    | Corrective Actions | Replace expansion valve |  HINT: For the example above, there is an expansion valve malfunction.
Pressure is too high on both low and high pressure side or pressure is too low on high pressure side
  
                              
                                 
                                 
                              
                              
                                 
                                    | Symptom | Air conditioning system does not cool effectively |  
                                    | Probable Cause | Internal leak in compressor |  
                                    | Diagnosis | Low compression |  
                                    | Leak from damaged valve or other compressor component |  
                                    | Corrective Actions | Replace compressor |  HINT: For the example above, there is insufficient compressor compression. (3) Gauge readings (Reference)   
                     
                        
                        
                        
                        
                     
                     
                        
                           | *a | Pressure on Low Pressure Side kPa (kgf/cm2, psi) | *b | Pressure on High Pressure Side kPa (kgf/cm2, psi) |  
                           | *c | Blower High Zone | *d | Blower Low Zone |  |